The Faudi P.4-1093 is a high-throughput coalescer found in depot and terminal filter-separators across Europe and export markets. Lefilter's equivalent is built for continuous bulk service: high dirt-holding capacity, stable pressure drop, and water shedding that holds up under flow surges — the three failure points of cheap aftermarket cartridges in terminal duty.
| End Cap Type | Model Code | Nominal Length (mm) | Nominal Length (inch) |
|---|---|---|---|
| P.1 (Flat Sealed, Special) | P.1-842 | 842 | 33 |
| P.3 (Flat Sealed, Open End) | P.3-279 | 279 | 11 |
| P.3-362 | 362 | 14 | |
| P.3-467 | 467 | 18 | |
| P.3-559 | 559 | 22 | |
| P.3-727 | 727 | 29 | |
| P.3-842 | 842 | 33 | |
| P.3-965 | 965 | 38 | |
| P.3-1093 | 1093 | 43 | |
| P.3-1422 | 1422 | 56 | |
| P.4 (Screw / Threaded Base) | P.4-279 | 279 | 11 |
| P.4-362 | 362 | 14 | |
| P.4-467 | 467 | 18 | |
| P.4-559 | 559 | 22 | |
| P.4-727 | 727 | 29 | |
| P.4-842 | 842 | 33 | |
| P.4-965 | 965 | 38 | |
| P.4-1093 | 1093 | 43 | |
| P.4-1422 | 1422 | 56 | |
| P.7 (Flat Sealed, Alternative Design) | P.7-362 | 362 | 14 |
| P.7-559 | 559 | 22 | |
| P.7-727 | 727 | 29 | |
| P.7-842 | 842 | 33 | |
| P.7-965 | 965 | 38 | |
| P.7-1093 | 1093 | 43 | |
| P.7-1422 | 1422 | 56 |
Gradient composite glass fiber pleated pack: high surface area for extended service intervals under particulate loading.
Filtration rating: 5 μm absolute particulate; coalescing optimized for sub-micron water droplet capture.
Continuous temperature: up to 107 °C (225 °F) with nitrile seals; 120 °C with fluorocarbon.
Pressure drop: media selected to match or slightly undercut the OEM ΔP curve at rated flow, so terminal throughput is not restricted.
Resin binder system prevents fiber shedding and media swelling in hydrocarbon service.
Refinery intermediate product filtration · pipeline terminal custody-transfer points · ship bunkering operations · depot filter-separators where OEM lead time or price is a constraint.
What micron rating does it carry? 5 μm absolute for solids, with coalescing tuned for sub-micron water mist.
Flat gasket or O-ring — which do I need? Match your existing Faudi housing; both variants are available, and the wrong seal style is the most common cause of bypass.
What is the temperature limit? 107 °C continuous with nitrile seals; 120 °C excursions with fluorocarbon.
Will pressure drop increase versus the original? No — the media is selected to meet or slightly undercut the OEM ΔP curve at rated flow.
| Item | Lefilter P.4-1093 Equivalent |
|---|---|
| Brand replaced | Faudi P.4-1093 |
| Element style | Pleated coalescer, 6″ diameter form factor |
| End seals | Flat gasket (standard Faudi configuration); O-ring variant on request |
| Seal material | Nitrile standard; fluorocarbon optional |
| Flow direction | Inside-to-outside |
Specify your end-cap variant at ordering — Faudi housings exist in both flat-gasket and O-ring sealing configurations, and the wrong choice causes bypass.
ONLINE MESSAGE